Series REGULUS - 6W0.3

6W0.3

Wound type current transformer

INFORMATION:

  • Weight approx. 200 - 270 g

ZUBEHÖR (IM LIEFERUMFANG ENTHALTEN):

  • 2 secondary terminal covers (yellow sliders)
  • 2 mounting feet 

Other ratios, burdens and accuracies on request.

OPTIONAL ACCESSORIES:

  • Snap-on mounting brackets for rail TS35 (DIN EN 60715)

SPECIAL DESIGNS (ON REQUEST):

  • Other primary and secondary currents
    Cast resin impregnation

GENERAL TECHNICAL DATA:

  • Maximum voltage for equipment Um = 0.72 kV (other voltages on request)
  • Rated power frequency withstand voltage 3 kV / 1 min (other voltages on request)
  • Rated frequency 50-60 Hz (other frequencies on request)
  • Thermal rated continuous current Icth = 1.2 x Ipr
  • Thermal rated short-time current Ith = 60 x Ipr
  • Rated dynamic impulse current Idyn = 2.5 x Ith
  • Instrument security factor FS5 to FS15
  • Service conditions Indoor application
  • Ambient temperature (operation) -40°C ... +60°C 
  • Ambient temperature (storage / transport) -40°C ... +60°C 
  • Insulation class H

Normative standards          

  • IEC 61869 Part 1 + 2                                              
  • DIN EN 42600

Enclosure                            

  • Break-proof polyamide                                             
  • Difficult to inflame

Secondary connection        

  • Nickel plated screws (2 Nm)                                           
  • Integrated secondary cover

Contact form

* Required field

Custom solutions: As individual as your application

Some applications have requirements that are beyond the capabilities of standard instrument transformers. In such cases we would appreciate to develop a your customised product or adapt existing products to your needed conditions or requirements. We will find the right solution to your application, too. Don’t hesitate to contact us!

more information